Huawei LUTERRA ESS sub-array with transformer station passes 80-hour fire test under SGS

In a test organized by SGS, a Huawei LUTERRA storage sub-array burned for 80 hours with an ignited 5-ton-oil transformer station; cell temperature stayed below 26°C, the company says.

Huawei LUTERRA ESS sub-array with transformer station passes 80-hour fire test under SGS
Photo: Kecko from Eastern Switzerland, Wikimedia Commons, CC BY 2.0 · License: CC BY 2.0

On October 30, 2026, Huawei Digital Power's LUTERRA Smart String Grid Forming ESS platform completed a sub-array-level large-scale fire test that included a transformer station, according to a Huawei release published on prnewswire.com on November 24, 2026 prnewswire.comprnewswire.comprnewswire.comOpen source ↗. The test was organized and run by SGS and witnessed by INERIS, Bureau Veritas, BCFI and the Tianjin Fire Research Institute of China's Ministry of Emergency Management. Huawei describes it as the first test of this kind in the industry.

INERIS helped define the abuse test conditions in line with the forthcoming French mandatory technical specification for outdoor stationary energy storage systems (AMPG 2925-2) and validated the results against it. The developer Corsica Sole witnessed the entire test.

Test setup and conditions

According to Huawei, large-scale fire tests in the industry mostly verify that fire does not spread between containers and do not cover complete arrays with their transformer stations. LUTERRA was first shown in June 2026 at Intersolar Europe. Huawei states that it offers higher energy density than other solutions, which places higher demands on safety.

The sub-array was built with minimum installation spacing, with 0.6 m between enclosures, and the containers were connected by through-busbars. The transformer station was ignited externally in a full-oil condition, with 5 ton of oil, to simulate an extreme thermal runaway scenario. The test ran without manual intervention prnewswire.comprnewswire.comprnewswire.comOpen source ↗.

Results after 80 hours of burning

The fire burned for 80 hours and reached a peak temperature of almost 1,000°C. Throughout the test, the cell temperature of the ESS containers in the sub-array stayed below 26°C, and the oil temperature in the adjacent transformer station remained below 28°C. Huawei reports that the fire was contained at the sub-array level and did not spread.

After the test, the main structure of the transformer station remained intact and could be safely hoisted and removed.

Huawei lists the earlier steps of its safety verification: positive-pressure oxygen-blocking and non-propagation verification of the Rock Pack, the PCS electrical safety test series, and ESS large-scale fire and container-to-container fire-isolation tests. The company says the sub-array design relies on coordinated protection across the whole sub-array, with system-level safety interlocking and redundancy prnewswire.comprnewswire.comprnewswire.comOpen source ↗.